banner
Certification
Datacom Cooling


Resources

Related Standards 1360 and 1361
Product-specific Operations Manual
General Operations Manual


Program Scope
This program applies to 60 Hz floor mounted Computer and Data Processing Room Air Conditioners (CDPR) of three (3) types: upflow air discharge, downflow air discharge and horizontal free air discharge, which utilize water, or chilled water, or HFC refrigerants.
 
Program Scope Exclusions:
For chilled water units:
  • CDPR with total cooling capacity greater than 253 kW;
  • CDPR with airflow rate greater than 36,000 cfm.
  • CDPR with flow rate greater than 180 gpm;
  • CDPR with THR greater than 317 kW.
  • Horizontal rooftop units

For air-cooled and water cooled units:
  • CDPR with total cooling capacity greater than 225 kW;
  • CDPR with airflow rate greater than 30,000 cfm.
  • CDPR with flow rate greater than 160 gpm;
  • CDPR with THR greater than 281 kW.
  • Horizontal rooftop units

Certified Ratings
  • Net Sensible Cooling Capacity at Rated Cooling Test A (Table 1 of AHRI Standard 1360), kW;
  • Net Sensible Coefficient of Performance Rating (NSenCOP) at Rated Cooling Tests A;
  • Airflow rate, scfm;
  • Fluid Flow Rate (for Water, and Chilled Water Units only), gpm; and
  • Fluid Economizer System Flow Rate (for Water, and Chilled Water Units only), gpm.